 |
Maximum Surge Current 3rd Party Tested per NEMA LS-1
25 - 300kA per mode, maximum single impulse ratings.
All modes protection L-N, L-G, N-G, L-L.
"weak link" eliminated - entire SPD surge path tested to ratings.
|
Robust MOV Technology
Industrial grade 40-48MM MOVs.
No "stacked" ratings of small electronic grade MOV arrays.
25 - 200kA per mode devices use (1 to 4) MOVs per mode.
250 - 300kA devices - (3 to 6) 40-48MM MOVs per mode. |
|
Patented Thermal Fuse Technology
|
| Industry Leading Longevity Characteristics
TR 7000 Series - 20,000 ANSI/IEEE Category C3 Impulses repetitive surges.
TR 5000 Series - Up to 5,000 ANSI/IEEE Category C3 impulses repetitive surges.
TR 7000 & 5000 Series - 5,000 ANSI/IEEE 500V, 2kA 10x1000micro sec. longwave repetitive surges. |
Excellent Surge Clamping Performance
Suppressed Voltage Ratings (SVR) for all levels of electrial distribution system including service
entrance, distribution and point of use locations.
|
Compact and Durable Wall Mounted Design
Smaller size and weight makes easier installation in tight electrical rooms.
Heavy guage steel enclosures, painted and stainless designs, surface and flush configurations with
optional fiberglass on NEMA 4X design.
|
UL1449, 3rd edition (September 2009) listed.
Click here to visit UL web site
UL 1283
CSA 22.2
ANSI / IEEE C62.21-1991(R1995)
ANSI / IEEE C62.45-2002
NEMA LS-1 - 1992 (R2000)
MIL-STD-220B
ANSI / NFPA 70B
NEC article 285
|
| Per Mode |
65kA - 300kA
|
| Per Phase |
130kA – 600kA |
| Surge Withstand |
65 and 200kAIC |
| Voltage |
120V to 600V |
| NEMA Ratings |
NEMA 1, 4, 4X, 12 |
|