Digital Energy Protection & Control Motor Protection
Protection & Control Online Store
Protection & Control Support
Protection & Control Press Room
Resources
  Brochures
  Manuals
  Software
  Specifications
  Support Documents
 
Related Links
  RMIO Remote I/O Module
  SR 3 Series
  EnerVista Software
  Training: Protective Relaying
  Training: IEC 61850
 
 

Designed for medium voltage motors in industrial applications, the 339 delivers unparalleled protection, control, diagnostics and communications in an industry leading draw-out construction. Providing simplified setup configuration through the use of the Motor Settings Auto-Configurator, advanced graphical diagnostics with the Motor Health Report and support for multiple communication protocols including IEC 61850, the 339 Motor Protection System provides unparalleled motor protection for most small and medium sized AC motors.

 
Key Benefits
  • Enhanced Thermal Model including RTD and current unbalance biasing
  • Time stamped event reports, waveform capture, motor start and motor trending
  • Security Audit Trail capturing setting and command changes
  • Powerful communication capabilities including USB, Serial, Fiber & copper Ethernet
  •  
  • Draw-out construction eliminates the need for FT test switches
  • Reduced wiring with support for remote RTD’s using the RMIO module
  • Simplified Motor Setup screen reduces setup and configuration time
  • Customized motor overload curve Flex curves
  • Detailed Motor Health Report with critical data
  • Applications    
  • Small to Medium sized Medium Voltage AC Motors
  • Protection of pumps, conveyors, fans, compressors, etc.
  •  
  • Harsh environments requiring protection against corrosive chemicals and humid environments
  • Applications requiring fast and secure communications

  •   Key Features    
     
  • Thermal model biased with RTD and negative sequence current feedback
  • Under Voltage
  • Over Voltage
  • Under/Over Frequency
  • Phase and ground TOC and IOC
  •  
  • Start supervision and inhibit
  • Mechanical Jam
  • Current Phase Reversal
  • Acceleration Time
  • Undercurrent / Underpower
  • Starts per Hour
  •   Protection & Control
      The 339 relay is a member of the 3 Series family of Multilin relays. This motor protective device is used to perform primary motor protection of medium voltage motor applications. The basic protection functions of this relay include motor thermal model, time-delayed and instantaneous overcurrent, ground overcurrent and sensitive ground overcurrent protection. Additional control features such as logic control are available for applications that require additional motor control functionality.

    The robust 339 streamlines user work flow processes and simplifies engineering tasks such as configuration, wiring, testing, commissioning, and maintenance. This cost-effective relay also offers enhanced features such as diagnostics, preventative maintenance, motor health reports and advance security features.
    345 Block Diagram
      Key Features    
     
  • Current, Voltage, Power, Frequency
  • Current Metering
  • RTD Temperature
  • Event Recorder: 256 events with 1ms time stamping
  • Oscillography with 32 samples per cycle and digital states
  •  
  • IRIG-B clock synchronization
  • Motor health diagnostics
  • Security audit trail
  •  
    Analyze power system disturbances with transient fault recorder and event records

     
     
     
     
    Preventative Maintenance:
    The 339 allows user to track relay exposure to extreme environmental conditions by monitoring and alarming at high temperatures.

    Failure Alarm
    The 339 detects and alarms on communication port and IRIG-B failures. The 339 also enables users to analyze system performance via diagnostics information such as event records, oscillography, etc.

    Statistical Data
    The 339 records statistical data in order to assist in diagnosing common motor faults, as well as assisting in planning preventative maintenance.

    Advanced Device Health Diagnostics
    The 339 performs comprehensive device health diagnostic tests during startup and continuously at runtime to test its own major functions and critical hardware. These diagnostic tests monitor for conditions that could impact and present device status via SCADA communications and front panel display.
     

    Providing complete detailed graphical diagnostic information is a first in the industry.The 339 provides the motor diagnostic information in a legible easy to use format that enables the user to make informed decision on the health of their motor.
     
      Key Features
     
  • 4 X20 character LCD display
  • Control panel with 12 LED indicator
  • Front USB and rear RS485 serial communications
  • Multiple Communication Protocols:IEC 61850, MODBUS TCP/IP, MODBUS RTU, DNP 3.0, IEC60870-5-104, IEC60870-5-103
  •  
     
    Easy integration into new or existing infrastructure. With several ethernet and serial port options, and a variety of protocols, the 350 provides advanced and flexible communication selections for new and existing energy management, SCADA, and DCS systems.

    The 339 utilizes the most advanced communication technologies today making it the easiest and most flexible motor protection relay to use and integrate into new and existing infrastructures. Multiple communication ports and protocols allow control and easy access to information from the 339. All communication ports are capable of communicating simultaneously. With our advanced draw-out construction, the 3339 relay can be drawn-out without having to disconnect any communication cables.

    The 339 supports the most popular industry standard protocols enabling easy, direct integration into electrical SCADA and HMI systems. Modbus RTU is provided as standard with a RS485 networking port. The following optional protocols are available:
  • IEC 61850
  • DNP 3.0
  • Modbus RTU
  • Modbus TCP/IP
  • IEC 60870-5-103
  • IEC 60870-5-104
  • These protocols make it easy to connect to a Utility or Industrial automation system, eliminating the need for external protocol converter devices.
     
     
     

     
     
    The Enervista suite is an industry leading set of software programs that simplifies every aspect of using the 339 relay. The Enervista suite provides all the tools to monitor the status of the protected asset, maintain the relay, and integrate the information measured into DCS or SCADA monitoring systems. Convenient COMTRADE and sequence of event viewers are an integral part of the 339 set up software and are included to ensure proper protection and system operation. Learn More
     
     
    Access Control
    Multilin devices and relays are designed with simple but powerful security to enable reliability and compliance for virtually any project or implementation. With support for multi-level permissions and multi-factor supervisory controls, Multilin devices can help you manage the integrity of your system during commissioning, testing, implementation, and beyond. The 3 Series family provides separate authentication for settings and commands to the system. In addition, as discrete authentications for local and remote access, it also provides a supervisory control factor that can lock or unlock a device for configuration changes and other modifications.
     
    Intrusion Detection
    Multilin’s family of protection and control products can also help enable your security perimeter and intrusion detection programs. By providing essential alarming and logging of critical events, Multilin devices can help you detect potential breaches within your system and allow you to respond quickly and effectively. Specifically, unsuccessful access attempts are logged, alarmed, and lead to potential attackers being locked out. This ensures the reliability of your system during questionable activity.
     
       
    Auditing and Reporting
    With the Security Audit Trail reporting feature and support for Event logging of key activities such as configuration changes, Multilin devices can help ensure device and protection system integrity, and perform forensic auditing of activities and changes for compliance.