The C60 Breaker Protection System is a substation hardened controller that provides a complete integrated package for the protection, control, and monitoring of circuit breakers. The C60 supports dual-breaker busbar configurations such as breaker-and-a-half or ring bus arrangements. Signals from up to 4 sets of CT’s can be brought into the C60 for internal summation
Complete breaker control, monitoring and integration in a single platform
Complete IEC 61850 Process Bus solution providing resource optimization and minimizing total P&C lifecycle costs
Reduced wiring through the use of high-speed peer-to-peer communication for accepting Trip and Close commands from other relays
Advanced automation capabilities for providing customized protection and control solutions
Ambient temperature monitoring with alarming when outside temperature exceeds upper thresholds
Robust network security enabling Critical Infrastructure Protection through user command logging, and dual permission access control
Modular hardware architecture allows for flexibility in device configurations to cover most breaker applications
Advanced fault and disturbance recording, including internal relay operating signals thus eliminating the need for external recording devices
Simplified system integration with communications supporting serial, Ethernet and multiple protocols
Embedded IEC61850 Protocol
The C60 supports English, French, Russian, Chinese and Turkish languages on the front panel
Stand-alone breaker monitoring and control
Multiple breaker configuration control including Breaker-and-a-Half and Ring Bus
Automatic Bus Transfer scheme using a single device
As part of a distributed bay controller
Breaker failure
Synchronism check
Autorecloser
Phase and Auxiliary undervoltage
Neutral and Auxiliary overvoltage
Phase, ground and neutral overcurrent
Sensitive directional power
Dual breaker control
The C60 Breaker Protection System is a substation hardened controller that provides a complete integrated package for the protection, control, and monitoring of circuit breakers. The C60 supports dual-breaker busbar configurations such as breaker-and-a-half or ring bus arrangements. Signals from up to 4 sets of CT’s can be brought into the C60 for internal summation which is advantageous by still having the individual currents available for metering and additional protection elements that operate on individual currents.
The C60 provides fast and deterministic execution of programmable logic and extensive I/O options that are necessary for substation automation applications.
All of the necessary control logic functions are available for creating automated breaker control schemes such as the popular Main-Tie-Main scheme using a single C60 device.
Metering - current, voltage, power, energy, frequency
Oscillography – analog and digital parameters at 64 samples/cycle
Breaker monitoring - accumulated wear and operation time, number of operations, breaker flashover and trip coil monitoring
Event Recorder - 1024 time tagged events with 0.5ms scan of digital inputs
Fault Locator
Setting Security Audit Trail for tracking changes to C60 configuration
The C60 is the single point for protection, control, metering, and monitoring in one integrated device that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint Monitoring as shown.
The C60 incorporates advanced automation features including powerful FlexLogic™ programmable logic, communication, and SCADA capabilities that far surpass what is found in the average breaker relay or controller. The C60 integrates seamlessly with other UR relays for complete breaker management including reclosing, load shedding, and synchronism applications.
Flexlogic™ allows for creating customized C60 breaker control schemes that include receiving Tripping and Closing commands from other devices and creating logic to replace the need for external lockout relays.
Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD)
Direct I/O – secure, high-speed exchange of data between URs for Direct Transfer Trip and pilot-Aided schemes
Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber optic ports and 2 copper ports
The C60 provides advanced commun-ications technologies for remote data and engineering access, making it easy and flexible to use and integrate into new and existing infrastructures. Direct support for fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available redundant Ethernet option and the embedded managed Ethernet switch provide the means of creating fault tolerant communication architectures in an easy, cost-effective manner without the need for intermediary communication hardware.
The C60 supports the most popular industry standard protocols enabling easy, direct integration into DCS and SCADA systems.
IEC 61850
DNP 3.0
Ethernet Global Data (EGD)
IEC 60870-5-104
Modbus RTU, Modbus TCP/IP
In addition to providing high-speed connectivity directly to your Universal Relay, the MultiLink UR Switch module provides an additional 4 Fiber Ethernet ports, for connection to other relays in the system as well as upstream connectivity. It also provides 2 RJ-45 copper Ethernet ports which can be used to connect local devices such as PCs, meters, or virtually anything else in the system.
The UR Switch provides a simple way to add fully-managed Ethernet networking to your relays and devices without the need for additional hardware or a dedicated communications cabinet.
The UR Switch includes all the management and features that come with all MultiLink managed switches, and can be easily integrated into a network that has other Ethernet switches.
When used in a ring topology with other UR switch modules or MultiLink switches, the UR Switch can be configured to use MultiLink’s Smart RSTP feature to provide industry-leading network recovery for ring topologies, at a speed of less than 5ms per switch. Learn More
Use the C60 with integrated IEC 61850 to lower costs associated with generator protection, control and automation. GE’s leadership in
IEC 61850 comes from thousands of installed devices and follows on years of development experience with UCA 2.0.
The C60’s IEC 61850 Process Bus module is designed to interface with the Multilin HardFiber System, allowing bi-directional IEC 61850 fiber optic communications. The HardFiber System is designed to integrate seamlessly with the existing Universal Relay applications, including protection functions, FlexLogic, metering and communications. Learn More
The EnerVista™ Suite is an industry-leading set of software programs that simplifies every aspect of using the C60 relay. The EnerVista™ suite provides all the tools to monitor the status of your the protected asset, maintain the relay, and integrate information measured by the C60 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR Setup software included with every UR relay, to carry out postmortem event analysis to ensure proper protection system operation. Learn More
Access Control
Multilin devices and relays are designed with simple but powerful security to enable reliability and compliance for virtually any project or implementation. With support for multi-level permissions and multi-factor supervisory controls, Multilin devices can help you manage the integrity of your system during commissioning, testing, implementation, and beyond.
The UR Family provides separate authentication for settings and commands to the system. In addition, as discrete authentications for local and remote access, it also provides a supervisory control factor that can lock or unlock a device for configuration changes and other modifications.
Intrusion Detection
Multilin’s family of protection and control products can also help enable your security perimeter and intrusion detection programs. By providing essential alarming and logging of critical events, Multilin devices can help you detect potential breaches within your system and allow you to respond quickly and effectively. Specifically, unsuccessful access attempts are logged, alarmed, and lead to potential attackers being locked out. This ensures the reliability of your system during questionable activity.control factor that can lock or unlock a device for configuration changes and other modifications.
Auditing and Reporting
With the Security Audit Trail reporting feature and support for Event logging of key
activities such as configuration changes, Multilin devices can help ensure device and
protection system integrity, and perform forensic auditing of activities and changes
for compliance.
Fully Compatible with GE's Multlilin HardFiber System
- Provides support for GE's
IEC 61850 HardFiber Process Bus Solution:
- Complete IEC 61850 Process Bus Solution providing resource optimization and minimizing total P&C lifecycle costs. Learn More
Security Enhancements - Enabling NERC CIP compliance:
- Dual Permission access requiring live permission from both the user and from SCADA operators before settings can be changed or commands can be given to the relay
- Logging of user commands in the security audit trail relay - creates a record and sequence of events for troubleshooting and security auditing
Ambient Temperature Monitoring:
- Provides alarms when the ambient temperature exceeds hot extreme
New and Enhanced IEC61850 services (FW version 5.90) - New user-configurable buffered report control block
- Extended GOOSE subscription functionality, up to 16 remote devices
New and Enhanced Protection and Control Functionality (FW version 5.90)
- Added Open pole Detector functionality
- Added Phase Overvoltage protection
- New Thermal overload element