F60 Feeder Management Relay

The F60, a member of the UR family of protection relays, is a digital relay that provides feeder protection and power metering in one integrated package. It may be used as a stand alone device or as a component an automated substation control system.

What's New in the F60:

Fully Compatible with GE's Multlilin HardFiber System - Provides support for GE's IEC 61850 HardFiber Process Bus Solution:
- Complete IEC61850 Process Bus Solution providing resource optimization and minimizing total P&C lifecycle costs
Security Enhancements - Enabling NERC CIP compliance:
- Dual Permission access requiring live permission from both the user and from SCADA operators before settings can be changed or commands can be given to the relay
- Logging of user commands in the security audit trail relay - creates a record and sequence of events for troubleshooting and security auditing
Ambient Temperature Monitoring:
- Provides alarms when the ambient temperature exceeds hot extreme

Features and Benefits
  • FlexLogic™ programmable logic
  • Virtual I/O (reduce hardware cost)
  • Expandable I/O
  • Flash memory for field upgrades
  • Optional user programmable pushbuttons
  • User programmable LEDs, fault reports, display messages, and self tests
  • Drawout modules for serviceability
  • Common modules (reduce spares cost)
  • Test mode for I/Os
  • IRIG-B time synchronization and repeater
Applications
  • Feeder protection and metering
  • Component in control system
Protection and Control
  • Phase, neutral, ground IOC
  • Phase, neutral, ground TOC
  • Sensitive ground IOC and TOC
  • 13 Standard curve shapes: (IEEE/IEC/IAC/I2t) or Flexcurve™
  • Phase, neutral and negative sequence directional
  • Wattmetric zero-sequence directional function
  • High impedance fault detection (Hi-Z)
  • Phase overvoltage
  • Phase undervoltage
  • Underfrequency
  • Autoreclose and synch check
  • Breaker failure
  • Tripping without Logic for direct tripping without the need for configuring Flexlogic Equations
  • Double Point Breaker/Switch Status
  • Incipient Cable Fault Detection
  • Breaker Restrike Detection
  • Enhanced Breaker Failure
Monitoring and Metering
  • Current, voltage, power metering
  • Current, voltage phasors
  • Frequency, harmonics
  • Transducer I/O
  • 64 samples/cycle oscillography
  • 1024 Event record
  • Data logging (8 channels)
User Interface
  • 2 x 20 character front panel display and keypad for local access
  • 48 programmable LED indicators
  • User-programmable pushbuttons providing local control
  • Multi-language support - French, Chinese, Russian options
  • EnerVista™ UR Setup software for configuration, monitoring and troubleshooting
Communications
  • Front Panel RS232 port
  • Up to two RS485 ports (up to 115 kbps)
  • Ethernet port: Redundant 10BaseFL or 100BaseFX fiber optics
  • Embedded Ethernet Switch for direct networking of UR devices
  • Inter-relay communications interfaces, RS422, G.703, IEEE C37.94
  • Direct I/O - Exchange inputs and outputs between relays with reduced wiring
  • Modbus RTU and TCP/IP
  • IEC61850
  • DNP 3.0 RTU and TCP/IP
  • IEC60870-5-104
  • Ethernet Global Data (EGD)
Security
  • Remote and Local Setting and Control passwords
  • Configurable lockout responses to unsuccessful password access attempts