T60 Transformer Protection System
The T60 is designed for various power applications, including auto-transformers, generator step up transformers, split-phase, angle regulating transformers and reactors. Uses multiple current and voltage inputs to provide primary protection and back-up protection of transformers, including differential, ground differential, phase, neutral, and ground overcurrent, under- and over-voltage, under- and over-frequency, over-fluxing, and breaker failure. T60 Buy Now
Key Benefits
  • Secure high-speed protection for transformers (IEEE C37.91)
  • Adaptive 2nd Harmonic Restraint algorithm
    improves security for energization and inrush
  • Integrated transformer thermal monitoring
  • Sensitive ground fault protection provides low impedance differential protection down to 5%
  • Advanced fault and disturbance recording, including internal relay operating signals
  •  
  • Advanced automation capabilities
  • Reduced relay to relay wiring and costs through high-speed inter-relay communications
  • Ambient temperature monitoring with alarming
    temperature exceeds thresholds
  • Complete IEC 61850 Process Bus solution minimizing total P&C life cycle costs
  • Robust network security enabling Critical Infrastructure Protection
  •      
    Applications    
  • Transformer asset monitoring using Hottest Spot, Loss-of-Life and Aging Factor
  • Reliable and secure protection for three-phase transformers, autotransformers, reactors, split phase and phase angle regulating transformers
  •  
  • Applicable for transformers with windings in a ring bus or breaker-and-a-half configuration
  • Stand-alone or component in automated substation control system

  •   Key Features    
     
  • Dual slope, dual breakpoint differential restraint characteristic restrained and unrestrained differential
  • 2nd harmonic inrush and overexcitation inhibit
  • Transformer overexcitation protection
  • Restricted ground fault
  •  
  • Loss-of-Life, Aging Factor, Hottest Spot
  • 3 zone back-up distance protection with power swing detection and load encroachment function
  • Synchrocheck
  •   Protection & Control
      The T60 Transformer Protection System is a comprehensive three-phase transformer relay designed to protect medium and large power transformers. The T60 provides automatic or user definable magnitude reference winding selection for CT ratio matching, and performs automatic phase shift compensation for all types of transformer winding connections. The T60 algorithm allows the user to enable removal of the zero-sequence current even for deltaa connected transformer windings, facilitating transformers with a variety of grounding configurations. As part of the Universal Relay (UR) Family, the T60 provides superior protection and control that includes:
    D60 Block Diagram
      Key Features
     
  • Metering - current, voltage, power, energy, frequency, temperature, transformer monitoring
  • Oscillography – analog and digital parameters at 64 samples/cycle
  • Event Recorder - 1024 time tagged events with 0.5ms scan of digital inputs
  • Data Logger - 16 channels with sampling rate up to 1 sample / cycle
  • Setting Security Audit Trail for tracking changes to T60 configuration
  •  
      The T60 includes high accuracy metering and recording for all AC signals. Voltage, current, and power metering are built into the relay as a standard feature. Current and voltage parameters are available as total RMS magnitude, and as fundamental frequency magnitude and angle. Also, harmonic measurements for voltage and current up to 25th for power quality applications.
    T60 can monitor, calculate and log hottest-spot temperature, aging factor and lost of life data over a long period. These data combined with economic analysis, allows criteria to be developed regarding the best time at which to replace a power transformer due to load growth, i.e. to minimize the cost without
     
    Multi-Breaker application example
     
     
     
    The T60 incorporates advanced automation features including powerful FlexLogic™ programmable logic, communication, and SCADA capabilities that far surpass what is found in the average transformer relay. The T60 integrates seamlessly with other UR relays for complete system protection.
     
    Flexlogic™ allows for customizing the T60 to operate and control the breakers and other auxiliary devices needed to fit most generator protection schemes and applications.
     
      Key Features
     
  • Networking interfaces – 100Mbit Fiber Optic Ethernet, RS485, RS232, RS422, G.703, C37.94
  • Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870-5-104, Ethernet Global Data (EGD)
  • Direct I/O – secure, high-speed exchange of data between URs for Direct Transfer Trip applications
  • Embedded Managed Ethernet Switch with 4 - 100 Mbit Fiber optic ports and 2 copper ports
  •  
     
    The T60 provides advanced commun-ications technologies for remote data and engineering access, making it the most advanced and flexible transformer protection relay to use and integrate into new and existing infrastructures. Direct support for fiber optic Ethernet provides high-bandwidth communications allowing for low-latency controls and high-speed file transfers of relay fault and event record information. The available redundant Ethernet option and the embedded managed Ethernet switch provide the means of creating fault tolerant communication architectures in an easy, cost-effective manner without the need for intermediary communication hardware. The T60 supports the most popular industry standard protocols enabling easy, direct integration into DCS and SCADA systems.
     
  • IEC 61850
  • DNP 3.0
  • Ethernet Global Data (EGD)
  • IEC 60870-5-104
  • Modbus RTU, Modbus TCP/IP
  •  
     
     
    In addition to providing high-speed connectivity directly to your Universal Relay, the MultiLink UR Switch module provides an additional 4 Fiber Ethernet ports, for connection to other relays in the system as well as upstream connectivity. It also provides 2 RJ-45 copper Ethernet ports which can be used to connect local devices such as PCs, meters, or virtually anything else in the system.
     

    The UR Switch provides a simple way to add fully-managed Ethernet networking to your relays and devices without the need for additional hardware or a dedicated communications cabinet.

    The UR Switch includes all the management and features that come with all MultiLink managed switches, and can be easily integrated into a network that has other Ethernet switches.

    When used in a ring topology with other UR switch modules or MultiLink switches, the UR Switch can be configured to use MultiLink’s Smart RSTP feature to provide industry-leading network recovery for ring topologies, at a speed of less than 5ms per switch. Learn More

     
     
    Use the T60 with integrated IEC 61850 to lower costs associated with generator protection, control and automation. GE’s leadership in
    IEC 61850 comes from thousands of installed devices and follows on years of development experience with UCA 2.0.
     
      The T60’s IEC 61850 Process Bus module is designed to interface with the Multilin HardFiber System, allowing bi-directional IEC 61850 fiber optic communications. The HardFiber System is designed to integrate seamlessly with the existing Universal Relay applications, including protection functions, FlexLogic, metering and communications. Learn More
     
     
    The EnerVista™ Suite is an industry-leading set of software programs that simplifies every aspect of using the G30 relay. The EnerVista suite provides all the tools to monitor the status of your generator, maintain your relay, and integrate information measured by the G30 into DCS or SCADA monitoring systems. Convenient COMTRADE and Sequence of Events viewers are an integral part of the UR Setup software included with every UR relay, to carry out postmortem event analysis to ensure proper protection system operation. Learn More
     
     
    Access Control
    Multilin devices and relays are designed with simple but powerful security to enable reliability and compliance for virtually any project or implementation. With support for multi-level permissions and multi-factor supervisory controls, Multilin devices can help you manage the integrity of your system during commissioning, testing, implementation, and beyond.
    The UR Family provides separate authentication for settings and commands to the system. In addition, as discrete authentications for local and remote access, it also provides a supervisory control factor that can lock or unlock a device for configuration changes and other modifications.
     
    Intrusion Detection
    Multilin’s family of protection and control products can also help enable your security perimeter and intrusion detection programs. By providing essential alarming and logging of critical events, Multilin devices can help you detect potential breaches within your system and allow you to respond quickly and effectively. Specifically, unsuccessful access attempts are logged, alarmed, and lead to potential attackers being locked out. This ensures the reliability of your system during questionable activity.control factor that can lock or unlock a device for configuration changes and other modifications.
     
       
    Auditing and Reporting
    With the Security Audit Trail reporting feature and support for Event logging of key
    activities such as configuration changes, Multilin devices can help ensure device and
    protection system integrity, and perform forensic auditing of activities and changes
    for compliance.

    Fully Compatible with GE's Multlilin HardFiber System - Provides support for GE's IEC 61850 HardFiber Process Bus Solution:
    - Complete IEC 61850 Process Bus Solution providing resource optimization and minimizing total P&C lifecycle costs.
    Learn More

    Multilink UR Ethernet Switch Module
    The UR Switch Module simplifies Ethernet networking in Substations and Industrial environments and can save users as much of 70% of the entire cost associated with installing Ethernet networks.
    Learn More
    Security Enhancements - Enabling NERC CIP compliance:
    - Dual Permission access requiring live permission from both the user and from SCADA operators before settings can be changed or commands can be given to the relay
    - Logging of user commands in the security audit trail relay - creates a record and sequence of events for troubleshooting and security auditing
    Ambient Temperature Monitoring:
    - Provides alarms when the ambient temperature exceeds hot extreme
    New Software options allow protection of Power Transformers with up to 5 windings / current sources
    The T60 Transformer Protection relay can now include a third CT/VT module (DSP) to protect power transformers with up to 5 current sources, making the T60 the right choice for complicated power transformer protection schemes, i.e. breaker and a half in the HV winding and multiple feeders in the LV winding (firmware version 5.70).
    New RRTD and RTD alarm and trip settings
    The T60 offers RTD alarm and trip settings to provide advanced monitoring of power transformers’ temperature. In addition, the RRTD module enables remote monitoring and metering of up to 12 programmable RTDs which reduces the number of RTD cables and provides temperature backup protection (firmware version 5.70). Learn More