Front and rear accessible
Vacuum circuit breaker design
Electrically interlocked for secure operation
Overcurrent protection on the generator source breaker
Compliance with ANSI/EEE spec C37
Drawout P.T. trunnion design on utility to facilitate removal of control fuses from rear of cabinet
Control module isolated from power section
Control module 25 provided for use with generator as an alternate source
Control circuit disconnect switch
System voltage 2.4 or 5kV
Interrupting current 16,000 amp
Making current 31,500 amp
Short Time Current 12,500 amp
Switching life 10,000/10,000 OP (load/no load)
System voltage 2.4-5kV 7.2-15kV
Rated current 1200-3000 amp
Interrupting and withstand current 25,000-49,000 amp 25,000-48,000 amp
Switching life 2000/10,000 OP (load/no load)